MOXA MGate 4101-MB-PBS
1-port Modbus RTU/ASCII to PROFIBUS slave gateways
- Protocol conversion between Modbus and PROFIBUS
- Windows utilities with innovative QuickLink function for automatic configuration within minutes
- Redundant dual DC power inputs and relay output supported
- Embedded data packet analyzer
- Powerful and visual diagnostic tool
- -40 to 75°C wide operating temperature models available
The MGate 4101-MB-PBS gateway provides a communication portal between PROFIBUS PLCs (e.g. Siemens S400 and S300 PLCs) and Modbus devices. With the QuickLink feature, I/O mapping can be accomplished within a matter of minutes. All models are protected with a rugged metallic casing, are DIN-rail mountable, and offer optional built-in optical isolation.
Windows Utilities for Easy Setup and Traffic Monitoring
The QuickLink windows utility uses a serial console port to connect to the MGate 4101-MB-PBS and makes configuration and operation as easy as possible. QuickLink can finish configuration in just few minutes by passively detecting Modbus requests with the AutoLearning function, and performing error-free I/O mapping with the AutoMapping feature. QuickLink drastically reduces Modbus-to-PROFIBUS integration time when compared to conventional I/O mapping, which can easily require days to complete. Additionally, embedded monitoring tools can maintain logs of Modbus communication packets and assist in troubleshooting.
Redundant Power Inputs
The MGate 4101-MB-PBS has dual power inputs for greater reliability. The power inputs allow simultaneous connections to two live DC power sources, so that continuous operation is provided even if one power source fails. The higher level of reliability makes these advanced Modbus-to-PROFIBUS gateways ideal for demanding industrial applications.
Warning by Relay Output
A relay output is provided for the power input status. The relay output gives maintenance engineers an additional tool for troubleshooting and maintenance.
Windows Utilities for Easy Setup and Traffic Monitoring
The QuickLink windows utility uses a serial console port to connect to the MGate 4101-MB-PBS and makes configuration and operation as easy as possible. QuickLink can finish configuration in just few minutes by passively detecting Modbus requests with the AutoLearning function, and performing error-free I/O mapping with the AutoMapping feature. QuickLink drastically reduces Modbus-to-PROFIBUS integration time when compared to conventional I/O mapping, which can easily require days to complete. Additionally, embedded monitoring tools can maintain logs of Modbus communication packets and assist in troubleshooting.
Redundant Power Inputs
The MGate 4101-MB-PBS has dual power inputs for greater reliability. The power inputs allow simultaneous connections to two live DC power sources, so that continuous operation is provided even if one power source fails. The higher level of reliability makes these advanced Modbus-to-PROFIBUS gateways ideal for demanding industrial applications.
Warning by Relay Output
A relay output is provided for the power input status. The relay output gives maintenance engineers an additional tool for troubleshooting and maintenance.
PROFIBUS Interface
Modbus Interface
Serial Signals
Software
Physical Characteristics
Environmental Limits
Power Requirements
Standards and Certifications
Reliability
Ordering Information
- Protocol
PROFIBUS DP-V0 Slave
Number of Ports
1
Data Rate
9600 bps to 12 Mbps
Connector
DB9 female
Isolation
2 kV (built-in)
DIP Switch
For termination
Rotary Switch
PROFIBUS address 0-99 (address 100-125 supported through software configuration)
Modbus Interface
- Protocol
Modbus RTU/ASCII Slave/Master
Number of Ports
1
Serial Standards
RS-232/422/485, software selectable
Connectors
DB9 male
ESD Protection
15 kV for all signals
RS-485 Data Direction Control
ADDC® (automatic data direction control)
Pull High/Low Resistor for RS-485
1 kÙ, 150 kÙ
Terminator for RS-485
120 Ù
Data Bits
7, 8
Stop Bits
1, 2
Parity
None, Even, Odd, Space, Mark
Flow Control
RTS/CTS, DTR/DSR (RS-232 only)
Baudrate
50 bps to 921.6 kbps
Serial Signals
- RS-232
TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422
Tx+, Tx-, Rx+, Rx-, GND
RS-485-4w
Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w
Data+, Data-, GND
Software
- Configuration Options
Serial Console, Windows Utility
Utilities
MGate Manager for Windows 2000/XP/2003/Vista/Server 2008/7/8 (x86/x64), Windows Server 2008 R2/2012 (x64)
Support
QuickLink, Paging
Physical Characteristics
- Housing
Metal, IP30 protection
Weight
500 g
Dimensions
36 x 105 x 140 mm (1.42 x 4.14 x 5.51 in)
Environmental Limits
- Operating Temperature
Standard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models:
-40 to 75°C (-40 to 167°F)
Storage Temperature
-40 to 85°C (-40 to 185°F)
Ambient Relative Humidity
5 to 95% (non-condensing)
Altitude
Up to 2000 m (795 hPa), higher altitudes on demand
Note
Please contact usif you require products guaranteed to function properly at higher altitudes.
Power Requirements
- Input Voltage
12 to 48 VDC
Power Connector
Terminal block
Power Consumption
MGate 4101-MB-PBS: 340 mA @ 12 VDC, 130 mA @ 48 VDC
MGate 4101I-MB-PBS: 375 mA @ 12 VDC, 140 mA @ 48 VDC
Standards and Certifications
- Safety
UL 60950-1, EN 60950-1
Hazardous Location
UL/cUL Class 1 Division 2 Groups A/B/C/D (Pending),
ATEX Zone 2 Ex nA nC IIC T3 Gc (Pending),
IECEx (Pending)
EMC
CE, FCC
EMI
EN 55022 Class A, FCC Part 15 Subpart B Class A
EMS
EN 55024,
EN 61000-4-2 (ESD) Level 3,
EN 61000-4-3 (RS) Level 2,
EN 61000-4-4 (EFT) Level 3,
EN 61000-4-5 (Surge) Level 3,
EN 61000-4-6 (CS) Level 2,
EN 61000-4-8 (PFMF) Level 1
Shock
IEC 60068-2-27
Freefall
IEC 60068-2-32
Vibration
IEC 60068-2-6
Reliability
- MTBF (mean time between failures)
513,139 hrs
Ordering Information
Available Modules | |
MGate 4101-MB-PBS | 1-port Modbus to PROFIBUS Slave gateway, 12-48 VDC, 0 to 60°C operating temperature |
MGate 4101I-MB-PBS | 1-port Modbus to PROFIBUS Slave gateway with 2 KV Isolation, 12-48 VDC, 0 to 60°C operating temperature |
MGate 4101-MB-PBS-T | 1-port Modbus to PROFIBUS Slave gateway, 12-48 VDC, -40 to 75°C operating temperature |
MGate 4101I-MB-PBS-T | 1-port Modbus to PROFIBUS Slave gateway with 2 KV Isolation, 12-48 VDC, -40 to 75°C operating temperature |
Kunder som tittade på denna vara tittade också på